As an Amazon Associate, we earn from qualifying purchases.
Price as of Oct 14, 2026. Product prices and availability are accurate as of the date indicated and are subject to change. Any price and availability information displayed on Amazon at the time of purchase will apply.
Disclaimer: This calculator provides preliminary estimates for educational purposes only. It is not a substitute for a licensed professional engineer, architect, or structural engineer. Results depend on material grade and species, site conditions, local climate and snow loads, and amendments to the applicable building code, all of which vary by location. Always verify results against your local building codes and confirm requirements with your Authority Having Jurisdiction before proceeding. Do not use these estimates for permitting, fabrication, or construction without stamped, engineer-sealed drawings from a licensed professional. Improperly sized structural members, foundations, or gas lines can cause structural collapse, fire, gas leaks, serious injury, or death.
Wire gauge depends on amperage (current draw), distance, and acceptable voltage drop. Higher amperage needs thicker wire (lower AWG number). Longer distances need thicker wire to prevent excessive voltage drop.
15A circuit: Minimum 14 AWG copper (most lighting and receptacles)
30A circuit: Minimum 10 AWG copper (dryers, water heaters)
40A circuit: Minimum 8 AWG copper (ranges, large appliances)
50A+ circuit: Minimum 6 AWG copper (subpanels, EV chargers)
Circuit Amps
Min Copper AWG
Max Distance (3% drop, 120V)
Common Use
15A
14 AWG
50 ft
Lighting, receptacles
20A
12 AWG
40 ft
Kitchen, bathroom
30A
10 AWG
30 ft
Dryer, water heater
40A
8 AWG
25 ft
Range, cooktop
50A
6 AWG
20 ft
Subpanel, EV charger
Q
What is voltage drop and why does it matter?
Voltage drop is the loss of electrical pressure as current travels through wire. Excessive drop (>3% for branch circuits, >5% total) causes equipment malfunction, dimming lights, and wasted energy. Longer runs need thicker wire.
NEC recommends max 3% drop for branch circuits (3.6V on 120V)
NEC recommends max 5% total from panel to load (6V on 120V)
Every doubling of distance doubles the voltage drop
Going up one wire size (e.g., 12 to 10 AWG) cuts drop by ≈40%
At 240V, the same wire carries the same amps with half the % drop
Q
What wire size for 20 amps?
For a 20-amp circuit, use 12 AWG wire for runs up to 50 feet. For longer distances, consider 10 AWG to minimize voltage drop. Always follow local electrical codes.
12 AWG copper: Safe for 20A up to 50 ft (2.9% drop at 120V)
10 AWG copper: Better for 50–100 ft runs (1.8% drop at 50 ft)
12 AWG resistance: 1.98 ohms per 1,000 ft
10 AWG resistance: 1.24 ohms per 1,000 ft
NEC Table 310.16: 12 AWG rated for 20A at 60°C termination
Q
What is the difference between AWG and mm²?
AWG (American Wire Gauge) is used in North America - lower numbers mean thicker wire. mm² is the metric standard measuring cross-sectional area. For example: 14 AWG ≈ 2.08 mm², 12 AWG ≈ 3.31 mm².
14 AWG = 2.08 mm² = 1.63 mm diameter
12 AWG = 3.31 mm² = 2.05 mm diameter
10 AWG = 5.26 mm² = 2.59 mm diameter
8 AWG = 8.37 mm² = 3.26 mm diameter
Each 3 AWG steps doubles the cross-sectional area
AWG
mm²
Diameter (mm)
Ampacity (Copper, 60°C)
14 AWG
2.08 mm²
1.63 mm
15A
12 AWG
3.31 mm²
2.05 mm
20A
10 AWG
5.26 mm²
2.59 mm
30A
8 AWG
8.37 mm²
3.26 mm
40A
6 AWG
13.30 mm²
4.11 mm
55A
4 AWG
21.15 mm²
5.19 mm
70A
Q
Should I use copper or aluminum wire?
Copper is more conductive, smaller, and easier to work with. Aluminum is cheaper but requires larger gauges for the same ampacity. Aluminum also needs special connectors and is typically used only for service entrances and feeders.
This calculator is provided for informational and educational purposes only. Results are estimates and should not be considered professional financial, medical, legal, or other advice. Always consult a qualified professional before making important decisions. UseCalcPro is not responsible for any actions taken based on calculator results.