Saturation vapor pressure (Magnus, Bolton 1980)
es(T) = 6.112 x exp(17.67 x T / (T + 243.5))Vapor pressure in hPa of saturated air at temperature T in Celsius.
Where:
T= Temperature in degrees Celsiuses= Saturation vapor pressure in hPaRelative humidity
58.3%
Dew point
59.4 °F
Vapor pressure
0.510 inHg
58.3%
59.4 °F
0.510 inHg
75.5 grains/lb
es(T) = 6.112 x exp(17.67 x T / (T + 243.5))Vapor pressure in hPa of saturated air at temperature T in Celsius.
Where:
T= Temperature in degrees Celsiuses= Saturation vapor pressure in hPae = es(Tw) - 0.00066 x (1 + 0.00115 x Tw) x P x (T - Tw)Actual vapor pressure of the air from the wet bulb reading, as used by the National Weather Service.
Where:
Tw= Wet bulb temperature, CT= Dry bulb temperature, CP= Station pressure, hPaRH = 100 x e / es(T)The share of the moisture the air could hold at the dry bulb temperature.
Inputs
Result
es at 23.89 C is 29.63 hPa and the vapor pressure works out to 17.27 hPa. 100 x 17.27 / 29.63 = 58.3%.
Inputs
Result
es(18 C) is 20.63 hPa. Taking off 0.00066 x 1.0207 x 1013.25 x 6 leaves 16.53 hPa, and 100 x 16.53 / 29.83 = 55.4%.
Inputs
Result
Lower pressure shrinks the correction term, so the vapor pressure rises to 17.91 hPa and RH to 60.4%.
A dry bulb of 75 F and a wet bulb of 65 F at sea level give 58.3% relative humidity and a 59.4 F dew point. We use the psychrometric equation from the National Weather Service: vapor pressure e = es(Tw) - 0.00066 x (1 + 0.00115 Tw) x P x (T - Tw), then RH = 100 x e / es(T).
First find the saturation vapor pressure at the wet bulb temperature. Subtract a correction that grows with the gap between the two thermometers and with air pressure, which gives the actual vapor pressure of the air. Divide that by the saturation vapor pressure at the dry bulb temperature and multiply by 100.
| Dry bulb | Wet bulb | RH | Dew point |
|---|---|---|---|
| 68 F | 60 F | 62.6% | 54.8 F |
| 72 F | 62 F | 56.6% | 55.8 F |
| 75 F | 65 F | 58.3% | 59.4 F |
| 85 F | 75 F | 62.8% | 70.9 F |
| 95 F | 75 F | 39.1% | 66.3 F |
It is the dry bulb reading minus the wet bulb reading. Water evaporates from the wick faster in dry air, which cools the wet bulb more, so a bigger depression means lower humidity. When the two thermometers read the same, the air is saturated at 100%.
| Wet bulb (dry bulb 75 F) | Depression | RH | Dew point |
|---|---|---|---|
| 75 F | 0 F | 100% | 75.0 F |
| 73 F | 2 F | 90.9% | 72.2 F |
| 70 F | 5 F | 78.0% | 67.7 F |
| 65 F | 10 F | 58.3% | 59.4 F |
| 60 F | 15 F | 40.5% | 49.4 F |
| 55 F | 20 F | 24.3% | 36.1 F |
Yes. Water evaporates from the wick more easily in thin air, so the wet bulb cools further for the same amount of moisture. The same two readings therefore mean more moisture at altitude. At 5,000 feet a 75 F and 65 F pair gives 60.4% instead of 58.3%. Use the station pressure, the actual pressure where you are, and leave out the sea level correction a weather report adds.
| Elevation (standard air) | Station pressure | RH at 75 F / 65 F | Dew point |
|---|---|---|---|
| Sea level | 29.92 inHg | 58.3% | 59.4 F |
| 1,000 ft | 28.86 inHg | 58.7% | 59.6 F |
| 3,000 ft | 26.82 inHg | 59.6% | 60.0 F |
| 5,000 ft | 24.90 inHg | 60.4% | 60.4 F |
| 8,000 ft | 22.23 inHg | 61.6% | 60.9 F |
Work out the actual vapor pressure e the same way as for relative humidity, then turn the saturation formula around. The dew point is the temperature at which e would be the saturation pressure: Td = 243.5 x ln(e / 6.112) / (17.67 - ln(e / 6.112)), in Celsius.
| Dry bulb | Wet bulb | Dew point |
|---|---|---|
| 20 C | 15 C | 11.6 C |
| 24 C | 18 C | 14.5 C |
| 30 C | 20 C | 14.5 C |
| 75 F | 65 F | 59.4 F |
| 80 F | 70 F | 65.2 F |
Wet the wick with clean water, ideally distilled, and move air past it: swing a sling psychrometer or run the fan on a powered one. Keep going until the wet bulb stops falling and read it straight away. A wick that dries out or gets no airflow reads too warm, and the humidity comes out too high.
| Problem | Wet bulb reads | RH comes out |
|---|---|---|
| Wick dried out | too warm | too high |
| Not enough airflow | too warm | too high |
| Dirty or crusted wick | too warm | too high |
| Sun on the thermometers | both too warm | unreliable |
Find the dry bulb reading on the left and the wet bulb depression across the top. Values are for sea level pressure (29.92 inHg) and come from the same formula as the calculator. Above sea level the true humidity is a little higher, so use the calculator with your station pressure.
| Dry bulb | 2 F | 4 F | 6 F | 8 F | 10 F | 15 F | 20 F |
|---|---|---|---|---|---|---|---|
| 50 F | 86.7% | 73.8% | 61.5% | 49.5% | 37.9% | 10.7% | - |
| 60 F | 88.8% | 78.1% | 67.7% | 57.8% | 48.2% | 25.8% | 5.2% |
| 70 F | 90.3% | 81.1% | 72.2% | 63.6% | 55.5% | 36.3% | 19.0% |
| 75 F | 90.9% | 82.2% | 73.9% | 65.9% | 58.3% | 40.5% | 24.3% |
| 80 F | 91.4% | 83.3% | 75.4% | 67.9% | 60.7% | 44.0% | 28.9% |
| 90 F | 92.3% | 84.9% | 77.8% | 71.1% | 64.6% | 49.6% | 36.1% |
| 100 F | 92.9% | 86.2% | 79.7% | 73.5% | 67.6% | 53.9% | 41.6% |
The same chart in Celsius at 1013.25 hPa. A depression of 1 C is about 1.8 F, so the columns do not line up with the Fahrenheit chart.
| Dry bulb | 1 C | 2 C | 3 C | 4 C | 6 C | 8 C |
|---|---|---|---|---|---|---|
| 10 C | 88.0% | 76.4% | 65.1% | 54.2% | 33.4% | 13.8% |
| 15 C | 89.8% | 79.9% | 70.3% | 61.1% | 43.5% | 27.1% |
| 20 C | 91.0% | 82.4% | 74.1% | 66.1% | 50.9% | 36.8% |
| 25 C | 92.0% | 84.3% | 76.9% | 69.8% | 56.4% | 43.9% |
| 30 C | 92.8% | 85.8% | 79.1% | 72.7% | 60.6% | 49.3% |
| 35 C | 93.4% | 87.0% | 80.8% | 74.9% | 63.8% | 53.5% |
Saturation vapor pressure comes from the Magnus formula with the constants Bolton published in 1980: es = 6.112 x exp(17.67 T / (T + 243.5)) hPa, with T in Celsius. Bolton fitted it to Wexler's more exact values, and it stays within 0.1 percent of them between -30 C and 35 C.
The psychrometric constant 0.00066 x (1 + 0.00115 Tw) per degree Celsius is the one used in National Weather Service calculations for a ventilated psychrometer. Printed psychrometric tables use slightly different constants, so they can differ from this page by a few tenths of a percent.
Last Updated: Nov 27, 2026
This calculator is provided for informational and educational purposes only. Results are estimates and should not be considered professional financial, medical, legal, or other advice. Always consult a qualified professional before making important decisions. UseCalcPro is not responsible for any actions taken based on calculator results.