Amps to kW, single phase
kW = A x V x PF / 1,000Real power in kilowatts from current, voltage and power factor. On DC, leave out PF.
Where:
A= Current in ampsV= Voltage in voltsPF= Power factor, from 0 to 1Power
4.8 kW
Watts
4,800
kVA
4.8
Circuit
1-phase, PF 1
4.8 kW
4,800 W
3.84 kW
4.8 kVA
kW = A x V x PF / 1,000Real power in kilowatts from current, voltage and power factor. On DC, leave out PF.
Where:
A= Current in ampsV= Voltage in voltsPF= Power factor, from 0 to 1kW = 1.732 x A x V x PF / 1,000A is the current in one line and V the voltage between two lines.
Where:
1.732= Square root of 3kVA = A x V / 1,000 (x 1.732 on three phase)The same product without the power factor. kW = kVA x PF.
Inputs
Result
20 x 240 x 1 / 1,000 = 4.8 kW. For a load that runs for hours, keep it to 80%, which is 3.84 kW.
Inputs
Result
32 x 230 x 1 / 1,000 = 7.36 kW, the figure behind the 7.4 kW label on European home chargers.
Inputs
Result
1.732 x 100 x 480 x 0.9 / 1,000 = 74.82 kW. Without the power factor it is 83.14 kVA.
kW equals amps x volts x power factor / 1,000, so 20 A at 240 V is 4.8 kW and 20 A at 120 V is 2.4 kW. For three phase, multiply by 1.732 as well: 100 A at 480 V and power factor 0.9 is 74.82 kW.
Multiply the amps by the voltage, then by the power factor, and divide by 1,000. A 20 A load at 240 V with a power factor of 1 is 20 x 240 / 1,000 = 4.8 kW. On DC the power factor drops out. On three phase you also multiply by 1.732.
| Amps | kW at 120 V | kW at 240 V |
|---|---|---|
| 15 A | 1.8 | 3.6 |
| 20 A | 2.4 | 4.8 |
| 30 A | 3.6 | 7.2 |
| 50 A | 6 | 12 |
| 100 A | 12 | 24 |
A 200 A home service at 240 V is 48 kW. The National Electrical Code limits continuous loads to 80% of a breaker's rating, so plan on about 38.4 kW you can draw for hours at a time. A 200 A three-phase service is 72.05 kW at 208 V and 166.3 kW at 480 V, at power factor 1.
| Service | kW | kW at 80% |
|---|---|---|
| 100 A, 240 V | 24 | 19.2 |
| 150 A, 240 V | 36 | 28.8 |
| 200 A, 240 V | 48 | 38.4 |
| 200 A, 208 V 3-phase | 72.05 | 57.64 |
| 200 A, 480 V 3-phase | 166.3 | 133 |
32 A at 230 V single phase is 7.36 kW, which is why a 32 A home EV charger in Europe is sold as a 7.4 kW unit. On a 400 V three-phase supply the same 32 A per phase gives 22.17 kW. In the US, 32 A at 240 V is 7.68 kW.
| Charger | kW |
|---|---|
| 16 A, 230 V | 3.68 |
| 32 A, 230 V | 7.36 |
| 40 A, 240 V | 9.6 |
| 48 A, 240 V | 11.52 |
| 32 A, 400 V 3-phase | 22.17 |
kVA is volts x amps / 1,000, the power the wiring has to carry. kW is the part that does work, kVA x power factor. They match for heaters and lights. Generators and transformers are often rated in kVA at a power factor of 0.8, so a 10 kVA generator delivers 8 kW.
| Power factor | kW for 30 A at 240 V |
|---|---|
| 1 | 7.2 |
| 0.95 | 6.84 |
| 0.9 | 6.48 |
| 0.85 | 6.12 |
| 0.8 | 5.76 |
Multiply 1.732 x amps x line-to-line volts x power factor and divide by 1,000. Use the current in one line wire. 100 A at 480 V with a power factor of 0.9 is 74.82 kW, and the same current on a 208 V system is only 32.42 kW.
| Amps per line | kW at 208 V | kW at 480 V |
|---|---|---|
| 10 A | 3.603 | 8.314 |
| 20 A | 7.205 | 16.63 |
| 50 A | 18.01 | 41.57 |
| 100 A | 36.03 | 83.14 |
| 200 A | 72.05 | 166.3 |
Values assume a power factor of 1. For a motor or anything with a lower power factor, multiply the chart value by it: 20 A at 240 V is 4.8 kW at PF 1 and 3.84 kW at PF 0.8.
| Amps | 120 V | 240 V | 208 V 3-phase | 480 V 3-phase |
|---|---|---|---|---|
| 1 | 0.12 | 0.24 | 0.3603 | 0.8314 |
| 5 | 0.6 | 1.2 | 1.801 | 4.157 |
| 10 | 1.2 | 2.4 | 3.603 | 8.314 |
| 15 | 1.8 | 3.6 | 5.404 | 12.47 |
| 20 | 2.4 | 4.8 | 7.205 | 16.63 |
| 30 | 3.6 | 7.2 | 10.81 | 24.94 |
| 40 | 4.8 | 9.6 | 14.41 | 33.26 |
| 50 | 6 | 12 | 18.01 | 41.57 |
| 60 | 7.2 | 14.4 | 21.62 | 49.88 |
| 100 | 12 | 24 | 36.03 | 83.14 |
| 150 | 18 | 36 | 54.04 | 124.7 |
| 200 | 24 | 48 | 72.05 | 166.3 |
Amps measure current and kilowatts measure power, so there is no fixed factor between them. Power is current times voltage, and the same 20 A is 0.24 kW on a 12 V battery and 4.8 kW on a 240 V circuit. Read the voltage off the nameplate or the panel before you convert.
On AC there is a third number, the power factor. Heaters, kettles and incandescent bulbs have a power factor of 1. Motors and compressors run lower, often around 0.8 to 0.9 at full load, and the nameplate usually lists it.
A breaker rating is a ceiling. For anything that runs 3 hours or more, the National Electrical Code wants the circuit sized at 125% of the load, which works out to using 80% of the breaker. A 50 A, 240 V circuit is 12 kW on paper and 9.6 kW for a continuous load like an EV charger.
To go the other way, from a known wattage to the current it draws, use the watts to amps calculator.
Read our guide
Read our guide
Read our guide
Wire gauge for a given current
Total load and circuits for an event
What moving to 200 A costs
Installed price by generator kW
Last Updated: Nov 27, 2026
This calculator is provided for informational and educational purposes only. Results are estimates and should not be considered professional financial, medical, legal, or other advice. Always consult a qualified professional before making important decisions. UseCalcPro is not responsible for any actions taken based on calculator results.