DC watts to amps
A = W / VCurrent equals power divided by voltage.
Where:
A= Current in ampsW= Power in wattsV= Voltage in voltsCurrent
8.333 A
kW
1
Volts
120
Circuit
1-phase, PF 1
8.333 A
1 kW
10.42 A
1 kVA
A = W / VCurrent equals power divided by voltage.
Where:
A= Current in ampsW= Power in wattsV= Voltage in voltsA = W / (V x PF)On AC, real power is volts x amps x power factor, so divide by both.
Where:
PF= Power factor, from 0 to 1 (1 for heaters and resistive loads)A = W / (1.732 x V x PF)Gives the current in each line wire, with V measured between two lines.
Where:
1.732= Square root of 3V= Line-to-line voltageInputs
Result
1,500 / (120 x 1) = 12.5 A. A heater can run for hours, so 12.5 x 1.25 = 15.63 A, which needs a 20 A circuit.
Inputs
Result
10,000 / (1.732 x 480 x 0.85) = 14.15 A in each line. The same load on 208 V three phase draws 32.66 A.
Inputs
Result
100 / 12 = 8.333 A. On a 24 V system the same light would draw half that, 4.167 A.
Amps equal watts divided by volts, so 1,000 W at 120 V draws 8.333 A and the same 1,000 W at 240 V draws 4.167 A. On AC, divide by volts x power factor, and on three phase divide by 1.732 x volts x power factor.
Divide the watts by the voltage. A 1,200 W microwave on a 120 V outlet draws 1,200 / 120 = 10 A. That simple form is exact for DC and for AC loads with a power factor of 1, such as heaters and kettles. For motors and other AC loads with a lower power factor, divide by volts x power factor instead.
| Watts | Amps at 120 V | Amps at 240 V |
|---|---|---|
| 500 W | 4.167 | 2.083 |
| 1,000 W | 8.333 | 4.167 |
| 1,500 W | 12.5 | 6.25 |
| 2,000 W | 16.67 | 8.333 |
| 5,000 W | 41.67 | 20.83 |
1,500 watts is 12.5 amps on a 120 V circuit and 6.25 amps on 240 V. 1,500 W is the usual top setting of a portable space heater, and because a heater can run for hours, the circuit should be rated for 125% of 12.5 A, which is 15.63 A. That puts it on a 20 A circuit.
| Voltage | Amps for 1,500 W |
|---|---|
| 12 V DC | 125 |
| 120 V | 12.5 |
| 208 V | 7.212 |
| 230 V | 6.522 |
| 240 V | 6.25 |
Multiply the breaker amps by the voltage: a 15 A, 120 V circuit carries 1,800 W and a 20 A circuit carries 2,400 W. A load that runs 3 hours or more counts as continuous under the National Electrical Code, and the circuit must be rated for 125% of it, so keep continuous loads to 80% of the breaker: 1,440 W on 15 A and 1,920 W on 20 A.
| Circuit | Max watts | Continuous (80%) |
|---|---|---|
| 15 A, 120 V | 1,800 | 1,440 |
| 20 A, 120 V | 2,400 | 1,920 |
| 30 A, 240 V | 7,200 | 5,760 |
| 40 A, 240 V | 9,600 | 7,680 |
| 50 A, 240 V | 12,000 | 9,600 |
On AC, a motor or a power supply draws current that does no useful work for part of each cycle, so it pulls more amps than its watts suggest. Power factor is the ratio of real watts to volts x amps. A heater has a power factor of 1. A motor at 0.8 draws 25% more current than a heater of the same wattage.
| Power factor | Amps for 1,000 W at 120 V |
|---|---|
| 1 | 8.333 |
| 0.95 | 8.772 |
| 0.9 | 9.259 |
| 0.85 | 9.804 |
| 0.8 | 10.42 |
Divide the watts by 1.732 x the line-to-line voltage x the power factor. The 1.732 is the square root of 3 and comes from the 120 degree offset between the phases. The answer is the current in each of the three line wires. A 10 kW load at 480 V and power factor 1 draws 12.03 A per line.
| Line-to-line voltage | Amps per line for 10 kW (PF 1) |
|---|---|
| 208 V | 27.76 |
| 240 V | 24.06 |
| 400 V | 14.43 |
| 480 V | 12.03 |
| 600 V | 9.623 |
Divide the watts by 12. A 100 W light bar draws 8.333 A from a 12 V battery. An inverter adds its own losses: at about 90% efficiency, a 1,000 W load pulls roughly 92.6 A from the battery instead of the 83.33 A the plain division gives, so size the cables and fuse for the higher number.
| Watts | Amps at 12 V | Amps at 24 V |
|---|---|---|
| 100 W | 8.333 | 4.167 |
| 250 W | 20.83 | 10.42 |
| 500 W | 41.67 | 20.83 |
| 1,000 W | 83.33 | 41.67 |
| 2,000 W | 166.7 | 83.33 |
Each value is watts divided by volts, with a power factor of 1. That covers DC and AC loads like heaters, kettles, toasters and incandescent bulbs. For a motor, use the calculator with its nameplate power factor, because the current will be higher than the chart shows.
| Watts | 12 V DC | 120 V | 240 V |
|---|---|---|---|
| 100 | 8.333 | 0.8333 | 0.4167 |
| 250 | 20.83 | 2.083 | 1.042 |
| 500 | 41.67 | 4.167 | 2.083 |
| 750 | 62.5 | 6.25 | 3.125 |
| 1,000 | 83.33 | 8.333 | 4.167 |
| 1,200 | 100 | 10 | 5 |
| 1,500 | 125 | 12.5 | 6.25 |
| 1,800 | 150 | 15 | 7.5 |
| 2,000 | 166.7 | 16.67 | 8.333 |
| 2,400 | 200 | 20 | 10 |
| 3,000 | 250 | 25 | 12.5 |
| 4,000 | 333.3 | 33.33 | 16.67 |
| 5,000 | 416.7 | 41.67 | 20.83 |
| 7,500 | 625 | 62.5 | 31.25 |
| 10,000 | 833.3 | 83.33 | 41.67 |
Watts are volts x amps on DC. On AC, the voltage and current rise and fall many times a second, and in a motor they don't peak together, so real watts are volts x amps x power factor. That is why the same 1,000 W can mean 8.3 A for a heater and over 10 A for a motor.
Three phase adds the square root of 3, about 1.732. Use the voltage between two lines (208, 240, 480 or 600 V in North America) and the answer is the current in each line. If you only know the voltage from a line to neutral, multiply it by 1.732 first.
The National Electrical Code treats a load that runs 3 hours or more as continuous and wants the circuit rated for 125% of it. Multiply the amps by 1.25 and pick a breaker at least that big. A 1,500 W heater at 120 V draws 12.5 A, and 12.5 x 1.25 is about 15.6 A, so it belongs on a 20 A circuit.
Wire size follows the breaker. Check the wire ampacity calculator for the gauge that matches, and add the other loads that share the circuit before you decide.
Read our guide
Read our guide
Read our guide
Wire gauge for a given current
How long a battery runs a load
Inverter size and 12 V battery draw
What a bigger panel costs
Last Updated: Nov 27, 2026
This calculator is provided for informational and educational purposes only. Results are estimates and should not be considered professional financial, medical, legal, or other advice. Always consult a qualified professional before making important decisions. UseCalcPro is not responsible for any actions taken based on calculator results.